0512-63326698

Air Outlet Series >> Displacement Air Outlet Series

SH-ZY Seat Air Supply Column

Product Description
Performance Parameter Table of FK-ZY Seat Air Supply Column
100 Air Volume (m³/h) 15 25 30 40
Pressure Loss (Pa) 1 2.5 3.5 6.5
Diffusion Distance (m) 0.15


Noise Level dB (A) 30 35
130 Air Volume (m³/h) 20 30 40 50
Pressure Loss (Pa) 1 2.2 4 6
Diffusion Distance (m) 0.2 0.3 0.4 0.5
Noise Level dB (A) 31 36
150 Air Volume (m³/h) 25 40 50 60
Pressure Loss (Pa) 1 2.5 4 6
Diffusion Distance (m) 0.2 0.3 0.4 0.5
Noise Level dB (A) 31 36
190 Air Volume (m³/h) 30 50 70 80
Pressure Loss (Pa) 1 2.7 5.5 7
Diffusion Distance (m) 0.2 0.3 0.5 0.6
Noise Level dB (A) 32 37
250 Air Volume (m³/h) 50 70 90 120
Pressure Loss (Pa) 1 2 3.5 6
Diffusion Distance (m) 0.15 0.4 0.6 0.8
Noise Level dB (A) 31 35
Notes:
All data in the table are tested based on isothermal airflow conditions.
The residual air velocity corresponding to the diffusion distance is 0.1 m/s.

previous: SH-ZY Seat Air Outlet

Next:Floor Diffuser

Message