Silencer Series >> Silencing Static Pressure Series

Resistive Silencer SHXJ-04

The resistive silencer absorbs sound energy by means of porous sound-absorbing materials laid inside the airflow passage, so as to reduce noise propagating along the duct. It delivers excellent silencing performance for medium and high frequency noise.

Product Description
Brief Introduction
The resistive silencer absorbs sound energy by means of porous sound-absorbing materials laid inside the airflow passage, so as to reduce noise propagating along the duct. It delivers excellent silencing performance for medium and high frequency noise.

Brief Introduction to Measured Performance of Silencer
Frequency 63 125 250 500 1000 2000 4000 8000 10000
Working Condition
Bare Duct Static State 65.0 71.0 95.5 97.0 90.5 90.5 77.5 60.5 84.5
3m/s 65.5 71.5 95.5 97.0 90.5 90.5 77.5 60.5 84.5
6m/s 66.5 71.0 95.5 97.0 90.5 90.5 78.0 60.5 84.5
9m/s 68.5 71.5 95.5 97.0 90.5 91.0 78.0 60.5 84.5
With Silencer Installed Static State 64.5 70.5 87.5 82.5 72.5 79.5 69.0 55.5 69.5
3m/s 64.5 71.0 87.5 82.5 71.5 79.5 69.5 55.0 69.5
6m/s 66.0 70.5 87.5 93.0 71.5 79.5 70.0 55.0 70.0
9m/s 68.0 71.0 87.5 93.0 71.5 80 70.0 55.0 70.0
Noise Reduction Static State 0.5 0.5 8.0 14.5 18.5 11.0 8.5 5.0 15.0
3m/s 1.0 0.5 8.5 14.5 19.0 11.0 8.0 5.5 15.0
6m/s 0.5 0.5 8.0 14.0 19.0 11.0 8.0 5.5 14.5
9m/s 0.5 0.5 8.0 14.0 19.0 11.0 8.0 5.5 14.5

Note: When the air velocity is 3 m/s, the pressure loss ΔH = 1.0 mmH₂O;
when the air velocity is 6 m/s, the pressure loss ΔH = 2.0 mmH₂O;
when the air velocity is 9 m/s, the pressure loss ΔH = 5.5 mmH₂O.