The SH-TF6A thermostatic linear diffuser features an integral elegant appearance. Its blades can be connected in any segmented form with flexible adjustment of airflow direction. Adopting eddy current airflow control, the diffuser delivers excellent performance including low pressure loss, low noise, relatively long jet range and rapid temperature difference elimination.
| Model | Number of Slots | Face Width Dimension(mm) | Neck Width Dimension(mm) |
| SH-TF6A | 1 | 65 | 35 |
| SH-TF6A | 2 | 100 | 70 |
| SH-TF6A | 3 | 134 | 103 |
| SH-TF6A | 4 | 168 | 138 |
| SH-TF6A | 5 | 202 | 172 |
| SH-TE6A | 6 | 236 | 206 |
SH-TF6A Thermostatic Linear Diffuser Air Outlet Performance Table
Slot (Group)
Neck Air Velocity (m/s)
1.5
2
2.5
3
3.5
4
5
Air Volume (m³/h)
105
140
175
211
246
281
351
SH -TF6A
Static Pressure Loss (Pa)
H
11
19
29
42
58
76
95
V
10
17
25
37
50
66
103
Diffusion Radius (m)
H
1.6
2.2
2.8
3.4
3.9
4.4
4.9
Effective Throw (m)
V
1.2
1.6
1.9
2.4
2.8
3.2
3.9
Noise Level dB (A)
H
—
—
—
20
21
22
38
V
—
—
22
28
31
35
45
SH -TF6A
Air Volume (m³/h)
210
280
350
422
492
562
702
Static Pressure Loss (Pa)
H
11
19
29
42
58
76
95
V
10
17
25
37
50
66
103
Diffusion Radius (m)
H
3
4
5.6
6.9
7.8
4.4
10
Effective Throw (m)
V
2.3
3
3.6
4.6
5.5
6.2
7.5
Noise Level dB (A)
H
—
—
—
21
22
23
42
V
—
—
23
34
37
41
47
SH -TF6A
Air Volume (m³/h)
315
420
525
633
738
843
1053
Static Pressure Loss (Pa)
H
11
19
29
42
58
76
95
V
10
17
25
37
50
66
103
Diffusion Radius (m)
H
4.8
6.5
7.2
8.1
9.3
10.5
11.5
Effective Throw (m)
V
3.5
4.5
5.5
6.2
6.8
7.6
9.3
Noise Level dB (A)
H
—
—
20
22
23
24
45
V
—
—
23
35
39
43
51
SH -TF6A
Air Volume (m³/h)
420
560
700
844
984
1124
1404
Static Pressure Loss (Pa)
H
11
19
29
42
58
76
95
V
10
17
25
37
50
66
103
Diffusion Radius (m)
H
5.1
7
8.6
10
12.1
13.8
15
Effective Throw (m)
V
3.8
5.1
6
7.6
9
10.2
12.5
Noise Level dB (A)
H
—
—
21
23
24
28
48
V
—
—
24
39
41
47
55
Notes:
(1) H stands for horizontal air discharge, and V stands for vertical air discharge. The throw distance and diffusion radius refer to the distance from the air outlet to the position where the wind speed is 0.5 m/s;
(2) The above table takes isothermal natural airflow as the test object;
(3) The vertical throw distance shall be corrected according to the air discharge temperature difference;
(4) All data in the above table are measured and tested based on an air outlet length of 1 meter.