0512-63326698

Air Outlet Series >> Displacement Air Outlet Series

SH-24 Crab-claw Linear Diffuser

It can be used for both air supply and air return. Each blade slot is equipped with two adjustable blades to control the airflow direction, volume and angle, which can be conveniently adjusted from the outside.

Product Description
Application and Characteristics
It can be used for both air supply and air return. Each blade slot is equipped with two adjustable blades to control the airflow direction, volume and angle, which can be conveniently adjusted from the outside.
This diffuser is generally installed on ceilings, and can also be mounted on side walls or other positions. It can be manufactured into an angled type according to different structural requirements.
Note: Custom size within 5.8 meters is available as a whole; sizes over 5.8 meters adopt a splicing structure.
Accessories: Plenum box, filter screen. 

SH-24 Crab-Claw Linear Diffuser Size Comparison Table
Model Number of Claws Face Width Dimension Neck Width Dimension
Inch Millimeter Inch Millimeter
SH-34 1 3 76.2 11/2 38.1
SH-34 2 41/2 114.3 3 76.2
SH-34 3 6 152.4 41/2 114.3
SH-34 4 71/2 190.5 6 152.5
SH-34 5 9 228.6 71/2 190.5
SH-34 6 101/2 266.7 9 228.6
SH-34 7 12 304.8 101/2 266.7
SH-34 8 131/2 342.9 12 304.8


FK-24 Crab-Claw Linear Diffuser Performance Table
Slot (Group) Static Pressure(mmH2O) 0.46 1.02 1.78 2.79 4.06 5.46 7.11 11.43
1 Air Volume (m³/h) per meter 111 167 223 278 334 390 446 557
NC
11 19 25 30 34 38 44
2 Air Volume (m³/h) per meter 223 334 446 557 669 780 892 1115
NC
14 22 28 33 37 41 47
3 Air Volume (m³/h) per meter 334 502 669 836 1003 1171 1338 1672
NC
16 24 30 35 39 43 49
4 Air Volume (m³/h) per meter 446 669 892 1115 1338 1561 1784 2230
NC
17 25 31 36 40 44 50
5 Air Volume (m³/h) per meter 557 863 1115 1393 1672 1951 2250 2787
NC
18 26 32 37 41 45 51
6 Air Volume (m³/h) per meter 669 1003 1338 1672 2007 2341 2676 3345
NC
19 27 33 38 42 46 52
7 Air Volume (m³/h) per meter 780 1171 1561 1951 2341 2732 3122 3902
NC
20 28 34 39 43 47 53
8 Air Volume (m³/h) per meter 892 1338 1784 2250 2676 3211 3568 4460
NC
20 28 34 39 46 47 53
NC-decibel: When the sound power is at 10−12, the attenuation of the room is 8 decibels.